In EMC, a well-shielded room designed to reduce reflections of electromagnetic waves and isolate the test setup from spurious influences. A fully anechoic chamber aims to absorb electromagnetic waves from all directions using RF absorbing materials while a semi-anechoic chamber (SAC) usually leaves the floor a bare, conductive metal material.
A piece of electronic test equipment that can generate very complex waveforms. Contrary to a signal generator or function generator, AWGs usually contain much more memory to store the complex waveform digitally.
Artificial Network (AN) – A device that can facilitate interaction between electrical systems and components, and often simulates the impedance of the real-world application or power.
Lightning strokes into high voltage power distribution systems are causing transients in low voltage power mains networks. Via coupling these transients can also be detected in data bus systems, I/O lines and any cabling in the industrial area. Parameters : Range of voltage some tens of kilovolts, range of current some tens of kilo amps, high-energy pulses with rise times in the microsecond range. Standard reference : IEC/EN 61000-4-5
Any subassembly or subsystem that is meant to be used with the DUT and supports testing of the main DUT, either by being a power or signal input, output, or load. An AE may be the real subassembly used in the application or simulated for the lab.
The usable frequency range of a programmable source, or amplifier. For RF amplifiers bandwidth is defined as the difference between the upper and lower frequency of operation (f2 - f1). For voltage sources, this is typically defined as the frequency where a -3 dB reduction in output signal compared to the nominal signal and normally starts at DC. Only signals within the frequency range of the operational bandwidth will be correctly amplified.
A type of conducted immunity test, mostly in the higher frequency ranges to ensure compliance and product reliability requirements. Typically used to simulate unintended nearby electrical disturbance that may be unintentionally coupled on the wires and cables.
ESD occurs when the static electric field between two objects exceeds the dielectric strength of the air between them. The discharge is a complex event involving a local transfer of charge at the point of discharge, electromagnetic near field coupling between the objects involved, induced current flow in the object receiving the discharge and radiated electromagnetic energy from the charged object as well as from the arc of the discharge. All of these phenomenon are capable of causing malfunctions and, in some cases, damage in electronic equipment. Parameters : The major effects are generated by the discharge current (< 100A) and voltage (< 30kV) with rise times in the nanosecond and even in the picosecond range. Standard reference : IEC/EN 61000-4-2
Ground shift tests are immunity tests whereby potential interference from conducted noise along a ESC’s power and signal grounds. This could be caused by faulty earthing or other coupling methods. One method usually used is coupling via a transformer, but the individual standards must be consulted to determine the recommended method. The NSG 5600 contains the necessary transformer.
With an increasing number of electronic power supplies used in a wide range of products the aim to limit the harmonic current emission has become more and more important. It is a specific interest of the power distribution companies to keep the harmonic current emission to a considerable low level as harmonic current causes unnecessary loading of the power distribution infrastructure. This again may affect both quality and reliability of the power supply. Parameters : Harmonic currents are measured up to the 40th harmonic of the fundamental. Limits for each harmonic are specified depending on the type of product. Standard reference : IEC/EN 61000-3-2, IEC/EN 61000-3-12
Depending on the coupling path, inverter noise can manifest itself in ripple on the power to certain DUTs that may be susceptible the the disturbance.
Lightning strikes into high voltage power distribution systems are causing transients in low voltage power mains networks. Via coupling these transients can also be detected in data bus systems, I/O lines and any cabling in the industrial area. Parameters : Range of voltage some tens of kilovolts, range of current some tens of kilo amps, high-energy pulses with rise times in the microsecond range. Standard reference : IEC/EN 61000-4-5